DANOPOL NI FV 1.2

Single Ply PVC-p 1. 2 mm membrane. Non UV Resistant.

Product variations:
Waterproofing
EPD S-P-00691 EPD S-P-00691
DANOPOL NI FV 1.2 is a synthetic PVC plasticized membrane, reinforced with Fibre glass mat. Designed for flat roof waterproofing. Non U.V. resistant.

Instruction for Use

Preparation of the substrate:
  • The surface of the base substrate shall be resistant, uniform, smooth, clean, dry and free of foreign bodies. In the case of thermal insulation, the boards shall be laid in a grid and without gaps of more than 1 mm between boards.
  • Polyester geotextiles, type Danofelt PY 300 or higher, shall be used as a separating or protective layer.
  • The dimensional stability of the DANOPOL FV sheet (≤ 0.09%) means that no perimeter anchoring is required in the horizontal plane in the execution of ballasted systems made with this sheet, in compliance with the UNE 104416 standard.
  • In the vertical plane, the profile is fixed so that the membrane rises a minimum of 20 cm above the surface of the pavement. A strip of sheeting is welded to the profile of the vertical facing and overlapped and welded to the membrane on the horizontal plane. It is recommended to use laminated profiles with a flange at the top, such as laminated profile B (with flange) for anchoring to the vertical facing. Stainless steel profiles, such as galvanised sheet metal, aluminium profiles, etc. can also be used.
  • The joint between the profile fixed to the facing and the brickwork facing is always sealed with an elastic and rot-proof mastic: ELASTYDAN PU 40 Grey.
Special points:
  • Where the roof meets vertical faces and elements passing through the membrane, the membrane must rise at least 20 cm above the finished roof level, or higher, if necessary, so that the top edge of the membrane is always above the maximum foreseeable water level on the roof. To improve the aesthetics of the finish on the vertical facing, the adhesive, GLUE-DAN PVC, can be used to adhere the sheet to the vertical facing.
  • To improve the strength of the overlaps, especially on green roofs, it is advisable to seal the overlap line using DANOPOL LIQUIDO in the same colour, applied with a bottle.
  • When the height of the parapet does not exceed 20 cm, or there is no perimeter parapet, the delivery to these parapets or edges of the slab can be made by means of a laminated sheet profile in the form of an angle, C-laminated profile (finishing angle with drip) that hangs on the outside of the facing in the form of a drip. This profile shall be fixed to the facing by its horizontal flange, which shall be wider than 6 cm, by means of anchors located at a distance of less than 25 cm from each other. The membrane shall be welded to the laminated sheet metal profile in such a way that the head of the screws is concealed.
Laying of the waterproofing membrane:
  • The membrane shall be laid perpendicular to the maximum slope line of the roof. The anchoring to the structural support shall be done by mechanical fastening. The joint between sheets shall be made by thermoplastic welding with a hot air welder. The overlaps shall be at least 10 cm to cover the mechanical fixing and the welding of the lower sheet with the upper one shall be at least 4 cm. Immediately after welding, the joint shall be pressed with a roller, thus ensuring a homogeneous joint. To check the joints, a blunt metal needle (with a rounded tip with a radius between 1 mm and 3 mm) shall be used to physically check the joints by passing it along the edge of the joint.
  • The rolls are laid loosely on the waterproofing substrate (thermal insulation or old waterproofing, in the case of renovation), starting at the lowest point of the roof slope and perpendicular to the line of maximum slope of the roof, forming a row of sheeting.
  • It is mechanically fastened in the longitudinal overlap area which is then covered by the next row of sheeting (highest part of the roof). The distance from the edge of the fastening washer to the edge of the sheet shall be greater than 1 cm.
  • The roll of the next row is laid out, welding the overlap where the fasteners are located. The sheets shall be laid in such a way that no transverse overlap of each row is aligned with any of those of the adjoining rows.
  • The roll of the next row is mechanically fixed on the other edge, with the same premises as described above. No anchoring line should be more than 2 metres away from the adjoining lines.
  • In the mechanical fastening, together with the waterproofing membrane, the underlay layers, such as vapour barrier, thermal insulation, etc., are fastened individually or simultaneously.
  • The sheet fixings at the perimeter of the roof must be aligned parallel to the perimeter of the roof.
  • No more than three sheets shall be joined at any one point.
  • At T-joints (three sheets intersecting at one point) the bottom sheet shall be chamfered to prevent capillary leakage or be reworked with the hot air welder.
  • The apex of the angle formed by the transverse and longitudinal edges of the top piece shall be cut into a curve.

Presentation

  • Length (cm): 2000
  • Length measurement standard: EN 1848-2
  • Width (cm): 180
  • Width measurement standard: EN 1848-2
  • Thickness (mm): 1,2
  • Product code: 210042
DANOPOL NI FV 1.2

Technical Data

Concept Value Standard
Mass per unit area (nominal) (kg/m²) 1.5 -
Density (kg/m³) 1250 -
Longitudinal elongation at break (%) > 200 -
Transversal elongation at break (%) > 200 -
External fire behaviour Froof EN 13501-5
Longitudinal & transversal dimensional stability < 0.09 EN 1107-2
Water vapour permeability (µ) 20.000 ± 30% EN 1931
Flexibility at low temperature (ºC) < -30 EN 495-5
Reaction to fire E EN 13501-1
Resistance to static loading (kg) >50 EN 12730 Método B
Resistance to root penetration Pasa EN 13948
Longitudinal & transversal tensile strength (N/5cm) > 600 EN 12311-2 Método A
Longitudinal & transversal tensile strength (N/mm²) > 10 -
Longitudinal resistance to tearing (nail shank) (N) > 120 EN 12310-2
Transversal resistance to tearing (nail shank) (N) >120 EN 12310-2
Resistance to impact, A (mm) > 500 EN 12691
Overlaps resistance (Shear of overlaps) (N/50mm) > 500 EN 12317-2
Overlaps resistance (Peeling of overlap) (N/50mm) > 220 EN 12316-2
Hazardous substances PND -

Addtitional Technical Data

Nominal minimum thickness 1.2 (-5%; +10%) EN 1849-2 Mass (kg/m²) 1,5 (-5%; +10%) EN 1849-2 Loss of elongation at break (UV 5000 h) < 10< 10 EN 1297, EN 12311-2EN 1297, EN 12311-2 Loss of plasticizers (mass change at 30 days) (%) < 4.5 EN ISO 177 Flatness (mm) < 10 EN 1848-2 Nominal minimum thickness 1.2 (-5%; +10%) EN 1849-2 Mass (kg/m²) 1,5 (-5%; +10%) EN 1849-2 Loss of elongation at break (UV 5000 h) < 10< 10 EN 1297, EN 12311-2EN 1297, EN 12311-2 Loss of plasticizers (mass change at 30 days) (%) < 4.5 EN ISO 177 Flatness (mm) < 10 EN 1848-2 Straightness (mm) < 50 EN 1848-2 Resistance to static punching (N) > 1200 UNE 104416 (b)

Environmental Information

Concept Value Standard
Post-consumer recycled content (%) NDP -
Pre-Consumer recycled content (%) NDP -
Manufactured in Fontanar - Guadalajara (España) -